Supply & installation of a 500kVA canopy generator set and ancillary equipment in the ground floor generator plant room, complete with 5,000 litre bulk fuel tank, housed in an adjacent space outside the plant room, with direct feed to the generator set.
Generator Supplied
HSW-500 T5 Canopy Generator Set
Additional Services
Supply and installation of a 5,000 litre direct supply bulk fuel tank
Additional secondary exhaust silencer, discharge attenuater and ductwork
GPA Involvement
The end result required was to successfully reduce the noise level of the standard HSW-500 T5 canopy Generator. Modifications were made to the canopy to be able to allow for vertical discharge which also included a discharge attenuator and ductwork to the facade of the plant room.
We also added a secondary silencer to ultimately achieve a noise level outside the plant room of 78dBA @ 7m. A 5000 litre bulk tank was installed just outside the generator plant room that supplied diesel direct to the generator set without the need for a fuel transfer system.